LOD levels (100–500) explained

The Level of Development scale used to say how far a model element has been developed and how much it can be relied on, from conceptual 100 to field-verified 500.
Updated 5 November 2026Draft · awaiting review

Level of Development (LOD) describes how far a model element has been developed, and so how much the people using the model can rely on it. It is set per element and per stage, not for a whole model. The scale is widely used in North America and on international projects, and is defined in the BIMForum Level of Development Specification.

At a glance

Defined byBIMForum LOD Specification (updated regularly); origins in AIA documents from 2008
Values100, 200, 300, 350, 400, plus 500 for field verification
Applies toEach element category, at each milestone
Recorded inAn LOD matrix, usually an appendix to the BEP
RelatedLevel of information need (ISO 7817-1), which replaces it in ISO 19650 contexts

The levels

LODMeaning in plain wordsReliable for
100A symbol or generic mass shows something is thereArea, volume and early cost studies
200A generic element with approximate size, shape and locationDesign development and early coordination
300A specific element with designed size, shape, location and orientationCoordination, drawings, quantities
350As 300, plus the interfaces with other systems (supports, connections, clearances)Detailed coordination between trades
400Detailed enough to fabricate and installFabrication, shop drawings, installation
500Verified in the field as installedRecord and handover (a statement of verification, not a further development step)

Each level also implies non-graphic information: at 300 a door has its dimensions and fire rating; at 400 its specific product.

Development is not detail

LOD is about reliability, not visual richness. A beautifully detailed manufacturer's object placed in roughly the right spot is still LOD 200 if its position and size are not designed. A plain box can be LOD 300 if its size and position are fixed and coordinated.

How it is used

Teams agree an LOD matrix: element categories down one side, milestones across the top, a target LOD and a responsible party in each cell. The matrix tells coordinators what can be clash-tested at each stage, tells estimators what can be measured, and tells contractors what they are taking over.

Common mistakes

  • One LOD for the whole model ("the model is LOD 300").
  • Confusing LOD with level of detail (sometimes also written LOD).
  • Asking for 400 at design stage for elements the designers do not specify.
  • No responsible party per cell, so nobody develops the element.
  • Assuming 500 means "more detail than 400". It means checked against what was built.

Where to read more

BIMForum publishes the LOD Specification with element-by-element descriptions and illustrations. For ISO 19650 projects, see LOD vs LOIN.

Discussion